SPI9000 Inverter Unit FR4 – FR8 User Manual
4-4 For more information visit: www.EatonElectrical.com
MN04004003E
April 2006
Figure 4-7: Option Board A3 Wiring Diagram
Control Cables
The control cables shall be at least 20 AWG screened multicore cables, see Table 4-1. The
maximum terminal wire size is 14 AWG for the relay terminals and 16 AWG for other
terminals.
You can find the tightening torques of the option board terminals in Table 4-1.
Table 4-1: Tightening Torques of Option Board Terminals
Galvanic Isolation Barriers
The control connections are isolated from the mains potential and the GND terminals are
permanently connected to ground. See Figure 4-8.
The digital inputs are galvanically isolated from the I/O ground. the relay outputs are also
double-isolated from each other at 300V AC (EN-50178).
26
25
23
22
21
RO1/1
RO1/2
RO1/3
RO2/1
RO2/2
R
L
Switching:
<8A / 24V DC
<2kVA / 250V AC
<0.4A / 125V DC
Continuously
<2 Arms
AC / DC
Basic Relay Board A3
29
28
TL1
+
+
t
TL1
Terminal Screw
Tightening Torque
lb-in.
Relay and thermistor terminals (screw M3) 4.5
Other terminals (screw M2.6) 1.8