SPI9000 Inverter Unit FR4 – FR8 User Manual
MN04004003E
For more information visit: www.EatonElectrical.com 2-7
April 2006
Fan Cooling
Frames FR4 to FR8
Enough free space must be left around the inverter to ensure sufficient air circulation and
cooling. You will find the required dimensions for free space in Table 2-6.
If several units are mounted on top of each other, the required free space equals C + D (Figure
2-6). Moreover, the outlet air used for cooling by the lower unit must be directed away from
the air intake of the upper unit. When planning the cooling for the space, take into
consideration that the inverter’s heat loss is 2.5% of the nominal capacity.
Figure 2-6: Installation Space
C
D
BB
A
A
2
A
A
2