Eaton Generator Manual de usuario Pagina 12

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 20
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 11
12
Technical Data TD00405018E
Effective August 2009
Generator Sizing Guide
EATON CORPORATION www.eaton.com
Worksheet — NEC 2008, 220 Part IV
Contractor Email
Phone Fax
Job Name
Date Location
Voltage (Circle) 240V -1Ø
Fuel NG LPV
Elec. Service 100 Amp 200 Amp 400 Amp Other
NET SQUARE FOOTAGE
General Loads Qty Rating (Load) Factor Loads (VA)
Loads (kW)
(VA ÷ 1,000)
General Lighting and General Use Receptacles 3 VA/ft² 100%
Branch Circuits (1500 VA/ft²)
Small Appliance Circuits (20 Amp) 1500 100%
Laundry Circuits 1500 100%
Fixed Appliances Full Current Rating
Well 100%
Sump Pump 100%
Freezer 100%
Microwave (Not counter-top model) 100%
Disposal 100%
Dishwasher 100%
Range (See Table 220.55 for multiple cooking appliances) 100%
Wall-Mounted Oven 100%
Counter-Mounted Cooking Surface 100%
Water Heater 100%
Clothes Dryer 100%
Garage Door Opener 100%
Septic Grinder 100%
Other (list) 100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
TOTAL GENERAL LOADS VA kW
Heat / A-C Load
A-C / Cooling Equipment 100%
Heat Pump
Compressor (if not included as A-C)
Supplemental Electric Heat
100%
65%
Electric Space Heating
Less than 4 separately controlled units
4 or more separately controlled units
65%
40%
System With Continuous Nameplate Load 100%
Largest Heat / A-C Load (VA) VA kW
General Loads
1st 10 kW of General Loads 100% kW 100% kw
Remaining General Loads (kW) 40% kW 40% kw
CALCULATED GENERAL LOAD (kW) kW kw
LARGEST HEAT / A-C LOAD 100% kW kW kw
TOTAL CALCULATED LOAD (Net General Loads + Heat/A-C Load) kw