Eaton Generator Manual de usuario Pagina 10

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 20
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 9
10
Technical Data TD00405018E
Effective August 2009
Generator Sizing Guide
EATON CORPORATION www.eaton.com
Onsite Estimating Sheet
Generator Sizing Instructions:
There is not a single correct sizing solution. Following are several methods
that, when mixed with good judgement, should result in an appropriately sized
generator. Remember to consider load growth, seasonality, and effects of
starting motors.
As municipalities and states adopt the new 2008 NEC Electrical Code, there
may be new sizing requirements, spelled out in the code book, which the
installation technician must follow. Always check with the local inspection
department to confirm which code cycle will affect your install.
Never add Amps when sizing a generator. Convert Amps to kW and add kW to
determine the required generator size. Power factors for various motor loads
vary widely. Adding Amps without properly accounting for the power factor
and/or mixing voltages will result in improperly sizing the generator.
When motors start, they create a current surge that step loads the generator
and creates a voltage dip. After selecting a generator, reference the
generators surge capability using table 3. Verify that voltage dip is adequate
for the application. Most commercial applications should be limited to about
15% voltage dip and residential applications should be limited to a 30%
voltage dip. Some applications utilize an uninterruptible power supply (UPS) to
back up critical loads. Please read sizing guide for this load type.
Measurement Method
Use a clamp-on Amp meter or power analyzer to measure facility load levels.
Clamp each leg separately and take the measurement during peak usage
levels.
240V 1ø Applications: To determine peak usage in kW, add the highest Amp
readings from the two legs, multiply by 120 and divide by 1,000.
(L1 + L2)120 / 1000
Size the generator 10 to 20% larger than the peak measured load.
Applications: Add the peak Amp readings from all three legs and divide by
3 to determine peak Amps. Multiply peak Amps by volts, multiply the result
by 1.732 (square root of 3), then divide by 1000 to convert Amps to kW.
Peak Amps = (L1 + L2 + L3) / 3
kW = [(Peak Amps x Volts) x 1.732] / 1000*
*Assumes power factor of 1.0
Size the generator 20 to 25% larger than the peak measured load.
Peak Amps = _____________ Peak kW= _____________
Billing History Method Commercial
Many commercial customers have a utility rate structure that has a peak
demand charge. Using a year’s worth of electric bills, size the generator 25%
larger than the largest peak demand.
Verify motor and UPS load compatibility: Peak Demand = _______
Load Summation Method
Enter running kW for all motor loads (except the largest) expected to run
during peak load levels into table 6. Refer to table 1 for typical motor load
sizes and electrical requirements.
Enter kW for all non-motor loads expected to run during peak load lev-
els into table 7. Refer to table 2 for typical residential loads and rules of
thumb.
Add the running motor load kW, non-motor load kW, and the starting kW
of the largest motor load.
Motor load running total (minus largest motor): _______________ kW
(ref. table 6)
Non-motor load total: (ref. table 7) _______________ kW
Starting load from largest cycling motor: _______________ kW
(ref. table 6)
Total electrical loads: = _______________ kW
Select generator: Commercial (add 20 to 25% to total kW)
Residential (add 10 to 20% to total kW)
Confirm that voltage dip is within acceptable limits by comparing motor
LRA to generator surge capability (see table #3).
Confirm UPS compatibility (see page 6).
System Capacity – Load Calculation
If the local municipality or state you are in has adopted the 2008 NEC Code,
you may be required to use this step. Article 702 of the 2008 NEC includes a
new requirement for sizing (702.5B). If no other method for sizing is accept-
able, sizing of the generator shall be made in accordance with Article 220 of
the NEC. The system capacity estimating sheet will guide you through this
process.
Project Layout
Ball Park Estimates (Do not use for final sizing)
Estimate based on 60% service size: (commercial)
240 Volts, 1 Ø: __________ Amps x .15 = __________ kW
208 Volts, 3 Ø: __________ Amps x .22 = __________ kW
240 Volts, 3 Ø: __________ Amps x .25 = __________ kW
480 Volts, 3 Ø: __________ Amps x .50 = __________ kW
Estimate based on 40% service size: (residential)
240 Volts, 1 Ø: __________ Amps x .10 = __________ kW
208 Volts, 3 Ø: __________ Amps x .15 = __________ kW
240 Volts, 3 Ø: __________ Amps x .17 = __________ kW
480 Volts, 3 Ø: __________ Amps x .34 = __________ kW
Estimate based on square footage
Fast food, convenience stores, kW = 50 kW + 10 watts/sq. ft.
restaurants, grocery stores
Other commercial applications kW = 30 kW + 5 watts/sq. ft.
Square footage = __________ Estimated kW = __________
Amps to kW Rule of Thumb (assumes .8 pf)
For 480 volt systems Amps = kW x 1.5
For 208 volt systems Amps = kW x 3.5
For 240 volt 3 Ø systems Amps = kW x 3
For 240 volt 1 Ø systems Amps = kW x 4
Vista de pagina 9
1 2 ... 5 6 7 8 9 10 11 12 13 14 15 ... 19 20

Comentarios a estos manuales

Sin comentarios